SMA Solar Technology AG

5  Single-Cluster System

Installation - Quick Reference Guide

Off-Grid-IS-en-30

27

B

AC power cable of the

generator

Sunny Island: terminal AC2 Gen/Grid terminals L, N, and PE
Generator: connect master to line conductor L1.
Conductor cross-section: maximum 16 mm²
For a single-phase system, the cable length and the conductor

cross-section must be identical on each Sunny Island.
The Sunny Island must be connected via a grounding conductor on the

terminal AC1 or AC2 to the ground potential. The conductor cross-section

of the grounding conductor must be 10 mm² or larger. If the conductor

cross-section is smaller, an additional grounding conductor on the

enclosure with the conductor cross-section of the AC power cable must

connect the Sunny Island with the ground potential.

C

DC+ cable

Battery terminal
For a single-phase system, the cable length and the conductor

cross-section must be identical on each Sunny Island.
Conductor cross-section: 50 mm² to 95 mm²
Cable diameter: 14 mm to 25 mm

D

DC − cable

E

Control cable, generator

Sunny Island: terminals Relay1 NO and Relay1 C
Conductor cross-section: 0.2 mm² to 2.5 mm²

F

Measuring cable of the

battery temperature sensor

Sunny Island: terminal BatTmp
You only have to connect a battery temperature sensor if lead-acid

batteries are used.
Mount the battery temperature sensor in the middle of the battery terminal,

in the upper third of the battery cell.

G

Control cable, load

shedding

Sunny Island: Connect control cable to terminals Relay2 NO and

BatVtgOut − .
Inside the Sunny Island inverter, connect terminals Relay2 C and

BatVtgOut+.
Conductor cross-section: 0.2 mm² to 2.5 mm²

H

RS485 communication bus

Sunny Island: at SI-COMSMA.BGx terminal ComSmaOut
Connection to other nodes, e.g., PV inverter
A terminator must terminate the RS485 communication bus on the last bus

node.

I

Data cable to

Sunny Remote Control

display

Sunny Island: Display terminal

K

Data cable for the internal

communication in the cluster

Sunny Island: ComSync Out terminal
Only with lithium-ion batteries: additional data cable on terminal

ComSync In
The communication bus must be equipped with a terminator on both ends.

L

RS485 communication bus

Sunny Island: at SI-COMSMA.BGx terminal ComSmaIn
Sunny WebBox: terminal SMACOM

Data cable to lithium-ion

battery

Only with lithium-ion batteries: additional data cable on terminal

ComSync In

Position

Designation

Description/information