beautypg.com

SMA Off-Grid Systems User Manual

Page 16

background image

3  Information on Off-Grid Systems and System Description

SMA Solar Technology AG

16

Off-Grid-IS-en-30

Installation - Quick Reference Guide

Sunny Island offers the following functions for off-grid systems via two multifunction relays (see the Sunny Island inverter

installation manual):

Battery current sensor

Shunt for measuring the battery current
A battery current sensor is required in off-grid systems with DC loads or with charge

controllers from third-party suppliers (see Section 2.1 "Intended Use", page 7).

Function

Description

Controlling generators

A multifunction relay activates if a generator request is received from the

Sunny Island inverter's generator management. With the multifunction relay, you can

control generators with electrical remote-start function or connect a signal generator

for generators with no autostart function.

Control of load-shedding

contactors

A multifunction relay is activated depending on the state of charge of the battery.

Depending on the configuration, you can install a one-stage load shedding with one

multifunction relay or a two-stage load shedding with two multifunction relays. You

can also adjust the limiting values for the state of charge of the battery depending

on the time of day.

Time control for external

processes

External processes can be time-controlled with a multifunction relay.

Display of operating states and

warning messages

You can connect message devices to the multifunction relays to allow operating

states and warning messages from the Sunny Island inverter to be output. One of the

following operating states and warning messages can be displayed for each

multifunction relay:

• The generator is running and is connected.
• A Sunny Island displays an error message of level 2 or higher. Only the error

messages within a cluster are evaluated here.

• A Sunny Island displays a warning. Only the warnings within a cluster are

evaluated here.

• The Sunny Island is in operation in a single system.
• The respective cluster is in operation in a cluster system.
• The Sunny Island is in derating in a single system.
• The respective cluster is in derating in a cluster system.

Control of a battery-room fan

The multifunction relay is activated when the charging current leads to the battery

emitting gases. A connected battery room fan is switched on for at least one hour.

Control of an electrolyte pump

Depending on the nominal energy throughput, the multifunction relay is activated at

least once a day.

Use of excess energy

During the constant voltage phase, a multifunction relay is activated and thus

controls additional loads that can put any excess energy of AC sources in the

stand-alone grid (e.g., of a PV system) to good use.

Device

Description