4  Single System

SMA Solar Technology AG

18

Off-Grid-IS-en-30

Installation - Quick Reference Guide

4.2 Connecting the Sunny Island

Figure 6: Connecting the Sunny Island inverter

Position

Designation

Description/information

A

AC power cable of the

stand-alone grid

Sunny Island: connection to AC1 Loads/SunnyBoys terminals L, N,

and PE
Conductor cross-section: maximum 16 mm²

B

AC power cable of the

generator

Sunny Island: connection to AC2 Gen/Grid terminals L, N, and PE
Conductor cross-section: maximum 16 mm²
The Sunny Island must be connected via a grounding conductor on the

terminal AC1 or AC2 to the ground potential. The conductor cross-section

of the grounding conductor must be 10 mm² or larger. If the conductor

cross-section is smaller, an additional grounding conductor on the

enclosure with the conductor cross-section of the AC power cable must

connect the Sunny Island with the ground potential.

C

DC+ cable

Battery terminal
Conductor cross-section: 50 mm² to 95 mm²
Cable diameter: 14 mm to 25 mm

D

DC − cable

E

Control cable, generator

Sunny Island: Relay1 NO and Relay1 C terminals
Conductor cross-section: 0.2 mm² to 2.5 mm²