2 connecting the slaves – SMA Off-Grid Systems User Manual

Page 28

background image

5  Single-Cluster System

SMA Solar Technology AG

28

Off-Grid-IS-en-30

Installation - Quick Reference Guide

5.3.2 Connecting the Slaves

Figure 11: Connecting the slaves in a single-cluster system

Position

Designation

Description/information

A

AC power cable of the

stand-alone grid

Sunny Island: connection to AC1 Loads/SunnyBoys terminals L, N, and PE

Stand-alone grid: Connect slave 1 to line conductor L2, and connect slave 2

to line conductor L3.
For a single-phase system, the cable length and the conductor cross-section

must be identical on each Sunny Island.
Conductor cross-section: maximum 16 mm²

B

AC power cable of the

generator

Sunny Island: connection of generator to AC2 Gen/Grid terminals L, N,

and PE
Generator: connect slave 1 to line conductor L2, connect slave 2 to line

conductor L3.
Conductor cross-section: maximum 16 mm²
For a single-phase system, the cable length and the conductor cross-section

must be identical on each Sunny Island.
The Sunny Island must be connected via a grounding conductor on the

terminal AC1 or AC2 to the ground potential. The conductor cross-section of

the grounding conductor must be 10 mm² or larger. If the conductor

cross-section is smaller, an additional grounding conductor on the enclosure

with the conductor cross-section of the AC power cable must connect the

Sunny Island with the ground potential.