6 minimum clearances, 1 minimum clearances for outdoor installation, Minimum clearances – SMA SC 500CP XT Installation User Manual
Page 71: Minimum clearances for outdoor installation

9.1.6
Minimum Clearances
9.1.6.1
Minimum Clearances for Outdoor Installation
Damage due to intake of exhaust air or blocked exhaust air outlets
The supply air is intended to cool the inverter components. Failure to observe the specified minimum clearances can
result in warm exhaust air from the inverter being drawn in. This increases the risk of a thermal short circuit. Property
damage due to yield loss and damage to the components may result.
• Ensure that no exhaust air can be drawn in through the air inlets.
• Ensure that it is not possible for exhaust air to be drawn into the air intake of other devices.
• Make sure that the exhaust air vents are not obstructed.
• Make sure that the exhaust air vents are accessible for cleaning at all times.
• Ensure that the minimum clearances are complied with.
Installation in closed electrical operating area
The inverter must be installed in a closed electrical operating area.
• Ensure that unauthorized persons have no access to the inverter.
Observe minimum clearances
Observe the minimum clearances to ensure trouble-free operation of the inverter.
Maintain a certain distance between inverters installed back to back. This will facilitate maintenance and cleaning.
Recommended clearance: 800 mm
Minimum clearances for one inverter
Figure 22: Minimum clearances for one inverter
9 Appendix
SMA Solar Technology AG
Operating Manual
71
SCCPXT-IA-E4-en-44