5 sunny central 800cp xt, Sunny central 800cp xt – SMA SC 500CP XT Installation User Manual
Page 60

8.5
Sunny Central 800CP XT
DC Input
Maximum DC Power
898 kW
Minimum input voltage / maximum input voltage
500 V to 1,000 V
Minimum MPP voltage
530 V
MPP voltage range at +25 C
641 V to 850 V
MPP voltage range at +50 C
583 V to 850 V
MPP voltage range at +25°C and 60 Hz
641 V to 850 V
MPP voltage range at +50°C and 60 Hz
583 V to 850 V
Rated input voltage
641 V
Maximum input current
1,400 A
Maximum short-circuit current
2,500 A
Maximum reverse current
2,300 A
Number of independent MPP inputs
1
Number of DC inputs
9
AC Output
Rated power at +25°C
880 kVA
Rated power at +50°C
800 kVA
Nominal AC voltage
360 V
Nominal AC voltage range
324 V to 414 V
AC power frequency
50 Hz / 60 Hz
AC power frequency range
47 Hz to 63 Hz
Rated frequency
50 Hz
Rated grid voltage
360 V
Maximum total harmonic distortion
0.03
Maximum AC current
1,411 A
Maximum residual current at the AC output
3,500 A
Maximum overcurrent protection at output
50,000 A
Power factor at rated power
1
Displacement power factor cos φ
0.9 overexcited to 0.9 underexcited
Feed-in phases
3
8 Technical Data
SMA Solar Technology AG
Operating Manual
SCCPXT-IA-E4-en-44
60