SMA SC 500CP XT Installation User Manual
Page 59
![background image](https://www.manualsdir.com/files/818313/content/doc059.png)
AC Output
Connection phases
3
Inrush current of the internal power supply
48 A (100 ms)
Efficiency
Maximum efficiency
98.6%
European weighted efficiency
98.4%
CEC weighted efficiency
98.5%
Protective Devices
DC overvoltage protection
Type I
Lightning protection as per IEC 62305-1
Lightning protection level III
Surge arrester for auxiliary power supply
Yes
Protection class in accordance with IEC 62103
I
Overvoltage category as per IEC 60664-1
III
General Data
Width x height x depth
2,562 mm x 2,272 mm x 956 mm
Weight
1,900 kg
Operating temperature range
−25°C to +62°C
Operating temperature range for low-temperature option
−40°C to +62°C
Noise emission at a distance of 10 m
60 db(A)
Self-consumption in operation
< 1,950 W
Standby consumption
< 100 W
External supply voltage
230 V / 400 V (3/N/PE), 50 Hz / 60 Hz
Degree of protection of electronics
IP54
Degree of protection of the connection area
IP43
Maximum permissible value for relative humidity (non-
condensing)
15 % … 95 %
Maximum operating altitude above mean sea level
2,000 m
Maximum operating altitude above MSL for option "In-
stallation at high altitudes"
4,000 m
Fresh air consumption
3,000 m³/h
8 Technical Data
SMA Solar Technology AG
Operating Manual
59
SCCPXT-IA-E4-en-44