4 climatic conditions, 5 equipment, 6 torques – SMA SB 3000TL User Manual
Page 52: 4 climatic conditions 11.5 equipment 11.6 torques
Maximum permissible fuse protection for
SB 3600TL-21
32 A
Maximum permissible fuse protection for
SB 4000TL-21
32 A
Maximum permissible fuse protection for
SB 5000TL-21
32 A
Ground-fault monitoring for SB 3000TL-21
Insulation monitoring: R
iso
> 625 kΩ
Ground-fault monitoring for SB 3600TL-21
Insulation monitoring: R
iso
> 550 kΩ
Ground-fault monitoring for SB 4000TL-21
Insulation monitoring: R
iso
> 500 kΩ
Ground-fault monitoring for SB 5000TL-21
Insulation monitoring: R
iso
> 400 kΩ
All-pole sensitive residual-current monitoring unit
Available
11.4 Climatic Conditions
Installation in accordance with IEC 60721-3-3, Class 4K4H
Extended temperature range
-25°C to +60°C
Extended humidity range
0% to 100%
Extended air pressure range
79.5 kPa to 106 kPa
Transport in accordance with IEC 60721-3-2, Class 2K3
Temperature range
-25°C to +70°C
11.5 Equipment
DC connection
SUNCLIX DC connector
AC connection
Spring-cage terminal
Display
LC graphic display
BLUETOOTH
As standard
Speedwire/Webconnect data module
As standard
RS485, galvanically isolated
Optional
Multifunction relay
Optional
SMA Power Control Module
Optional
11.6 Torques
Upper enclosure lid screws
6 Nm ± 0.3 Nm
Lower enclosure lid screws
2 Nm ± 0.3 Nm
11 Technical Data
SMA Solar Technology AG
Operating Manual
SB30-50TL-21-BE-en-11
52