General Data
Width x height x depth, with DC load-break
switch plugged in
661 mm x 682 mm x 264 mm
Weight
61 kg
Length x width x height of the packaging
780 mm x 380 mm x 790 mm
Transport weight
68 kg
Climatic category in accordance with IEC
60721-3-4
4K4H
Environmental category
Outdoors
Pollution degree outside the enclosure
3
Pollution degree inside the enclosure
2
Operating temperature range
-25°C to +60°C
Maximum permissible value for relative humid-
ity, non-condensing
100%
Maximum operating altitude above mean sea
level (MSL)
3,000 m
Typical noise emission
51 dB(A)
Power loss in night mode
1 W
Topology
Transformerless
Cooling method
SMA OptiCool
Degree of protection for electronics in accor-
dance with IEC 60529
IP65
Protection class in accordance with
IEC 62109-1
I
10 Technical Data
SMA Solar Technology AG
Operating Manual
45