SMA 20000TL User Manual
Page 44

STP 20000TL-30
STP 25000TL-30
Total harmonic distortion of the output
current with total harmonic distortion
of the AC voltage < 2%, and AC
power > 50% of the rated power
≤3%
≤3%
Rated power frequency
50 Hz
50 Hz
AC power frequency*
50 Hz / 60 Hz
50 Hz / 60 Hz
Operating range at AC power fre-
quency 50 Hz
44 Hz to 55 Hz
44 Hz to 55 Hz
Operating range at AC power fre-
quency 60 Hz
54 Hz to 65 Hz
54 Hz to 65 Hz
Power factor at rated power
1
1
Displacement power factor, adjustable
0
overexcited
to 0
underexcited
0
overexcited
to 0
underexcited
Feed-in phases
3
3
Connection phases
3
3
Overvoltage category in accordance
with IEC 62109-1
III
III
* depending on the configured country data set
Efficiency
STP 20000TL-30
STP 25000TL-30
Maximum efficiency, η
max
98.4%
98.3%
European weighted efficiency, η
EU
98.0%
98.1%
Protective Devices
DC reverse polarity protection
Short-circuit diode
Input-side disconnection point
DC load-break switch
DC overvoltage protection
Surge arrester type II (optional)
AC short-circuit current capability
Current control
Grid monitoring
SMA Grid Guard 3
Maximum permissible fuse protection
50 A
Ground fault monitoring
Insulation monitoring: R
iso
> 250 kΩ
All-pole sensitive residual-current monitoring unit
Available
10 Technical Data
SMA Solar Technology AG
Operating Manual
STP20-25TL-BE-en-12
44