4. Next, find the wire size according to the distance between your power supply and the sign and the total
current in the following table:
Distance
Total Current (Amps)
1-20
21-40
41-60
61-80
81-100
1-15 feet
10
10
8
6
6
16-30 feet
10
8
6
4
4
31-50 feet
8
6
4
2
2
Wire Gauge (AWG)
Example:
10 High Density BRICK Sign, 16-30 feet from power supply
•
Determine total current = 10 Bricks × 4.8 Amps = 48 Amps(previous calculation)
•
From table, 16-30 feet, 41-60 Amps, results in 6-gauge wire.
Service and Maintenance
The BRICK® Sign System is designed, manufactured, and assembled to require minimum maintenance.
Because of the operating environment the BRICK system is in, some maintenance is required. The table
below lists the items in the BRICK system that require maintenance, and the recommended interval for
providing that maintenance. The recommended intervals are based on average times from previous operat-
ing systems. The intervals for your system may vary from the recommended intervals because of your
operating environment.
Note
&
&
Before performing any maintenance on the system, please read and
follow all instructions in
Important Safety Information section