Damper Force Modes

Damper Force Modes are available for testing or balancing the system.
These Force Modes can be accessed and programmed from either the
System Manager or the Modular Service Tool.

System Manager Instructions

To access the Damper Force Modes from the System Manager, press
the “Setpoints” key. You will then see the unit ID screen. Enter the unit
ID of the controller you wish to access and press "Enter". The following
screen will appear.

1)Change Setpoint
2)Configure Unit

3)Damper Force

ESC) Exit Menu

Press “3” on the keypad and then the "Enter" key. You will then see the
unit ID screen. Enter the unit ID of the controller you wish to access
and press "Enter". At this time the password screen will be displayed.
Enter your level 2 password. Press "Enter" and the damper force modes
screen will be displayed.

1)Outputs Force
2)Dampers Force

Press the “2” key to access the Damper Force Modes screen. Outputs
Force is not available with the System Manager.

Modular Service Tool Instructions

When using the Modular Service Tool simply press the “Balance-Test”
key. You will then see the unit ID screen. Enter the unit ID of the con-
troller you wish to access and press "Enter". The damper force modes
screen will be displayed.

1)Outputs Force
2)Dampers Force

Press the “2” key to access the Damper Force Modes screen. Outputs
Force is available with the Modular Service Tool but is not used with
the VAVBOX controller.

Damper Force Mode Screens

If the unit ID you entered is for a WMVAV controller that has VAVBOX
controllers connected to its communication loop, the Damper Force
Mode will act as a “Global” Damper Force Mode. That is, all VAVBOX
controllers on that WMVAV controllers communication loop will be
forced to the same Damper Force Mode setting. If the unit ID you en-
tered is for a VAVBOX controller, the Damper Force Mode setting will
only apply to that VAVBOX controller.

Damper Force ID 159
Enter Force Mode.: 0

0=Auto 1=Open 2=Clsd

3=Max 4=Min 5=Fixd

Set the appropriate Damper Force Mode by entering numbers 0 through
5. The Force Modes for each of these settings is outlined below.

0 = Auto

This is the default setpoint. With this setting
the damper will operate normally and modulate
according to the controller setpoints.

1= Open

This setting will force the dampers to their fully
open position.

2= Clsd

This setting will force the damper to it’s fully
closed position.

3= Max

This setting will force the damper to the dampers
maximum airflow position set under Setpoint
Screen #4

4= Min

This setting will force the damper to the current
modes, minimum position setpoint. These modes
are Vent Mode, Heat Mode and Cool Mode. They
may each have a different minimum depending on
how you configured the setpoints.

5=Fixd

This setting will force the damper to a fixed
position based on the fixed position setpoint.

See VAVBOX controller Setpoint Screen #7 for
available setpoint information.

Caution: The Damper Force Modes should only be used by quali-

fied service personnel. Serious damage to the ductwork
could result if the dampers are all forced closed and
the HVAC unit fan is operating.