Setpoint Screen #13

WMVAV Spts ID 59
Economizer Setpoints

Min Position.: xx %

Control Rate.: xx

If the Economizer is not enabled or currently required during the occu-
pied mode of operation, the outside air dampers will maintain the Min
Position
setpoint to provide ventilation into the space.

The Control Rate can be used to speed up or slow down the operation
of the outside air dampers to prevent hunting. Unless you actually wit-
ness this damper hunting it is not recommended that the Control Rate
value be changed. Large values speed up the damper, and small values
slow down the damper.

Description

Minimum

Default

Maximum

Min Position

0 %

10 %

100 %

Control Rate

10

90

99

Setpoint Screen #14

WMVAV Spts ID 59
Static Spt..: x.xx”

Deadband....: x.xx”

Control Rate: xx Sec

The WMVAV controller uses the Fan VFD signal to maintain the Static
Spt
(duct static pressure) value plus or minus the Deadband value.
Adjustments to the signal are made at a rate equal to the Control Rate
setpoint, which can be used to speed up or slow down the signal to
prevent hunting.

Description

Minimum

Default

Maximum

Static Spt

0.10” WG

0.50” WG

3.0” WG

Deadband

0.01” WG

0.10” WG

1.0” WG

Control Rate

1 Sec

10 Sec

30 Sec

Setpoint Screen #10

WMVAV Spts ID 59
Heating Stages Off

If Supply Fan VFD Is

Below:.........: xx%

If the Supply Fan VFD drops below this value, the heat will stage off.
The Supply Fan VFD will not be allowed to drop below this value while
the unit is in Heating Mode unless the static pressure rises 0.5” above
the static setpoint.

Description

Minimum

Default

Maximum

Below SP

0 %

30 %

100 %

Setpoint Screen #11

WMVAV Spts ID 59
Pre-Heat Output ON

Continuous Below OAT
Level........: xx

°

F

If your air handler has at least one heating stage and you require a low
ambient protection or preheating of the air stream, you can enter a sup-
ply temperature value that causes one stage of heating to come on and
remain on continuous if the outdoor air drops below this level. If you
don’t want this protection do not configure any relays for this function.

Description

Minimum

Default

Maximum

Low Ambient Level

-50

°

F

0

°

F

70

°

F

Setpoint Screen #12

WMVAV Spts ID 59
Economizer Setpoints
OAT/WB Enable: xx

°

F

If the Outdoor Air Temperature drops below the OAT/WB Enable
(Outdoor Air Temperature or the optional Wetbulb Temperature, if
it’s available), the Economizer will be enabled to operate as the first
stage of cooling anytime there is a demand for cooling. If the econo-
mizer is currently in a control mode, it will attempt to maintain the
Supply Air Temperature at the Supply Air Cooling Setpoint.

Description

Minimum

Default

Maximum

OAT/WB Enable

-30

°

F

55

°

F

80

°

F

Programming The WMVAV Controller