Setpoint Screen #5

WMVAV Spts ID 59
Both Heating/Cooling

Supply Control Use
Deadband Of.: xx

°

F

All heating and cooling stages are staged up and down based on the
Heating/Cooling Supply Control Staging Deadband setpoint that is en-
tered on this screen. The value that is entered here will be added to the
Supply Air Temperature Setpoint to determine the high end of the range
and subtracted from the Supply Air Temperature Setpoint to determine
the low end of the range. Staging of Heating/Cooling will occur above
and below this deadband range. When the temperature is within this
deadband range, no staging will occur.

Description

Minimum

Default

Maximum

Deadband

0

°

F

1

°

F

20

°

F

Setpoint Screen #6

WMVAV Spts ID 59
Morning WarmUp Setup
Target Temp: xx

°

F

Max Length.: xxx Min

If you need a Morning Warm-up period on your HVAC unit enter a
Target Temp you want the Return Air Temperature to achieve and the
Max Length of time you want to spend in warm-up mode trying to
achieve the target temperature. If you don’t need morning warm-up,
simply ignore the Target Temp setpoint and enter a ‘0’ for the Max
Length value.

Description

Minimum

Default

Maximum

Target Temp

50

°

F

72

°

F

90

°

F

Max Length

0

Min

60

Min

240

Min

Setpoint Screen #7

WMVAV Spts ID 59
Outdoor Air Lockouts
Cooling:.....: xx

°

F

Heating:.....: xx

°

F

If the Outdoor Air Temperature drops below the Cooling lockout set-
point by 1°F, the DX cooling will be locked out until the Outdoor Air
Temperature rises 1°F back above the lockout setpoint. The same 1°F
deadband applies to the Heat lockout setpoint except the Outdoor Air
locks out the heating when it is above the lockout instead of below the
lockout.

Description

Minimum

Default

Maximum

Cooling

-30

°

F

50

°

F

80

°

F

Heating

50

°

F

75

°

F

90

°

F

Setpoint Screen #8

WMVAV Spts ID 59
All Cooling Cuts Off

If Supply Air Temp
Drops Below: xx

°

F

If the Supply Air Temperature ever drops below this value, all cooling
stages are immediately cutoff, regardless of run time. If the economizer
is being controlled, it is also closed completely to prevent freezing.

Description

Minimum

Default

Maximum

Low Cutoff

30

°

F

40

°

F

60

°

F

Setpoint Screen #9

WMVAV Spts ID 59
All Heating Cuts Off

If Supply Air Temp
Exceeds....: xxx

°

F

If the Supply Air Temperature ever exceeds this value, all heating stages
are immediately cutoff, regardless of run time.

Description

Minimum

Default

Maximum

High Cutoff

60

°

F

170

°

F

250

°

F