Setpoint Screen #23

WMVAV Spts ID 59
Push-Button Override

Duration....: x.x Hr

If the Space Temperature sensor contains the optional push-button over-
ride then this is the amount of time the unit will revert to occupied
operation whenever the button is pressed during the unoccupied mode.

Description

Minimum

Default

Maximum

Duration

0.0 Hr

2.0 Hr

8.0 Hr

Setpoint Screen #24

WMVAV Spts ID 59
Slide Offset Sensor
Setpoint....: x

°

F

If Space Temperature is used as the controlling sensor for the HVAC
unit and it is supplied with the optional Setpoint Slide Adjust, this is
the maximum amount the user can adjust the heating and cooling set-
points up or down as the slide is moved from the center position to its
full up or down position.

Description

Minimum

Default

Maximum

Slide Offset Setpoint

0

°

F

0

°

F

6

°

F

Setpoint Screen #25

WMVAV Spts ID 59
Air to Air Heat Pump

Delay Before Using

Aux Heating.: xx M

If you configured this air handler to control as an Air to Air Heat Pump
unit and you have auxiliary heating on this unit, you can adjust how
long the unit uses the compressor to attempt to provide heating before
it activates the Aux Heat to supplement the compressor.

Note: On Air to Air Heat Pumps you must configure one of the

relays to be used as the Reversing Valve. This output is
active anytime the unit is in the heating mode and this
mode is the only time the Aux Heat will be activated, if
needed.

Description

Minimum

Default

Maximum

Aux Heating Delay

0 Min

3 Min

30 Min

Setpoint Screen #20

WMVAV Spts ID 59
AHU Scheduled By

Schedule Number: x

0=AHU 1-7=Scheduler

Normally, the HVAC unit will use its own internal time clock and week
schedules to set the occupied mode of operation. If you have several air
handlers you can connect an external scheduling device to the commu-
nications loop and program the air handler for the desired schedule to
follow. If the HVAC unit is using its internal schedule, enter a ‘0’ for the
Schedule Number.

Description

Minimum

Default

Maximum

Schedule Number

0

0

1 to 7

Setpoint Screen #21

WMVAV Spts ID 59
Maximum Economizer

Position if High CO2

Level Occurs.: xxx %

If you have configured the air handler to read a CO

2

sensor, it will

override the minimum economizer position up to this position if the
CO

2

level rises above its setpoint by the adjustable Reset Rng amount.

See Setpoint Screen #22.

Note: Minimum Position determined by user adjustable Min

Position Setpoint on Setpoint Screen #13.

Description

Minimum

Default

Maximum

Max Position

See Note

100%

100%

Setpoint Screen #22

WMVAV Spts ID 59
CO2 Protection Limit

Max Level.: xxxx PPM

Reset Rng.: xxxx PPM

If you configure the air handler to read a CO

2

Sensor, the Max Level is

the point at which the economizer minimum position starts to reset
upward. As the CO

2

level rises above the Max Level by the Reset Rng

amount, the economizer will have reset its minimum position propor-
tionally up to the previously defined economizer maximum damper
position setpoint.

Description

Minimum

Default

Maximum

Max Level

0 PPM

900 PPM

5000 PPM

Reset Rng

0 PPM

100 PPM

1000 PPM

Programming The WMVAV Controller