Operator interfaces technical guide 33 – WattMaster VAV System User Manual

Page 33

background image

Operator Interfaces

Technical Guide

33

Status Screen #4

HC Box v1.04 IDxxxx
Supply Air.: xx.x

°

F

Duct Air...: xx.x

°

F

Line 2

Current Supply Air Temperature received via
broadcast from the WMVAV controller or from the
VAVBox Controllers own installed Supply Air Sensor
on the AUX2 input.

Line 3

Current Duct Air Temperature at the
duct air temperature sensor location if a duct
temperature sensor is installed and connected to the
VAVBOX controller. If a duct air temperature sensor is
not installed this line will display the same supply air
temperature as on Line 2 above.

Status Screen #5

HC Box v1.04 IDxxxx
Damper FRC: xxx %

Airflow...: xxxx CFM

Desired...: xxxx CFM

Line 2

Current Zone Damper Position If the user has entered
a FORCE command, the letters FRC will appear. If
this is normal damper operation, the FRC is not
displayed.

Line 3

If this is a Pressure Independent box, the current
Airflow will be displayed. If not, this line will display
the current damper position.

Line 4

If this is a Pressure Independent box, this line will
display the Desired CFM the box would like to
provide to the zone. If not, this line will display
[Controls to +/- 3%] to indicate how accurately the
damper will maintain the desired position.

Status Screen #6

HC Box v1.04 IDxxxx
Fan Status : OFF

1 Reheat Stages On

Line 2

If this is a Fan Powered box, this line will display the
Fan On/Off Status. On non fan powered boxes, this
line will display: Exp Relay 1 Not Used

Line 3

If your VAV Box Controller has been configured to
control reheat stages, this line reflects the On/Off
Status of the first stage of Reheat. If proportional
heating is used this line will display “Heating
Signal: xxx %
”. If you have 3 stages of reheat this
line will display the total number of active heating
stages.

Example:

“1 Reheat Stages On” or

“2 Reheat Stages On” or

“3 Reheat Stages On”

Line 4

Blank

Status Screen #7

HC Box v1.04 IDxxxx

NO ALARMS!

Line 2

Blank

Line 3

NO ALARMS!

This is displayed if no alarms are detected. If there are
one or more alarms active, the possible messages are
shown below:

SPACE SENSOR FAILURE

CFM SENSOR FAILURE

DAMPER OPENING ALARM

DAMPER CLOSING ALARM

HI SPACE TEMP ALARM

LO SPACE TEMP ALARM

DPR FEEDBACK FAILURE

Line 4

Blank