Programming the wmvav controller, Technical guide operator interfaces 22, Status – WattMaster VAV System User Manual

Page 22

background image

Technical Guide

Operator Interfaces

22

Programming The WMVAV Controller

Status

The WMVAV controller status screens are accessed by pressing the
“Status” button on either the System Manager or the Modular Service
Tool. Following are the available status screens and a description of
their functions.

Status Screen 1

WMVAV v1.00 ID 59
Occupied Mode
Venting Mode
Normal Operation

Line 2

Line displays one of the following:

Unoccupied Mode

Remote Signal ON

Occupied Mode

Override Mode

Holiday Mode

Zone Demand!

Forced Schedule Mode

OUTPUT FORCE MODE!

SUPPLY AIR CUTOFF!

High CO2 Level Mode!

Line 3

If you selected Supply Air as the controlling sensor, this
line will display:

Supply Air Control

If you select Space Temp or Return Air Control the
display will show one of the following:

Venting Mode

Cooling Mode

Heating Mode

Dehumidify Mode

Line 4

Line displays one of the following:

Normal Operation

Fan Starting Delay

xx Left in WarmUp (Number of Minutes Left)

Status Screen 2

WMVAV v1.00 ID 59
Cooling Enabled

Heating Disabled

Economizer Enabled

Line 2

Line displays one of the following:

Cooling Enabled

Cooling Disabled

Line 3

Line displays one of the following:

Heating Enabled

Heating Disabled

Line 4

Line displays:

Economizer Enabled

Economizer Disabled

Status Screen 3

WMVAV v1.00 ID 59
Temperature: x

°

F

Cooling Spt: xx.x

°

F

Heating Spt: xx.x

°

F

Line 2

Current Controlling Temperature

Can be Supply Air, Return Air or Space Temperature

Line 3

Currently active Cooling Setpoint

Based on the current Occupied / Unoccupied mode of
operation.

Line 4

Currently active Heating Setpoint

Based on the current Occupied / Unoccupied mode of
operation. If the Supply Air Sensor is the controlling
sensor, this will indicate the Night Setback temperature that
the Space Temperature uses to bring on heat during the
unoccupied mode.

Status Screen 4

WMVAV v1.00 ID 59
H/C Demand: xx.x

°

F

Space Temp: xx.x

°

F

CO2 Level.: xxxx PPM

Line 2

Current Heating or Cooling Demand

Based on the comparison between the Controlling
Temperature and the Heating and Cooling Setpoints. A
positive number indicates a cooling demand and a
negative number indicates a heating demand.

Line 3

Current Space Temperature reading.

This sensor is only used during unoccupied hours unless it
has been configured as the Controlling Sensor.

Line 4

Current CO

2

Level.

If you configured for a CO

2

Sensor, this line will display the

CO

2

Level. Otherwise, it will remain blank.

S

S

S

S

Status Screen 5

WMVAV v1.00 ID 59
Outdoor Air: xx.x

°

F

Humidity...: xx.x %
Wetbulb....: xx.x

°

F

Line 2

Current Outdoor Air Temperature.