Operator interfaces technical guide 27 – WattMaster VAV System User Manual
Page 27
Operator Interfaces
Technical Guide
27
Unit xxx Does Not
Support The Function
Press Any Key To
Continue
If you entered the unit ID of a WMVAV controller the following screen
will be displayed.
1)Outputs Force
2)Dampers Force
Press the “1” key to access the Outputs Force screen.
Supply Fan Override
Enter Override...: 0
[0=Auto 1=ON 2=OFF]
The first Outputs Force screen allows the Supply Fan relay to be set for
Auto, ON or OFF by entering a 0, 1 or 2 as desired. The default setting
is 0=Auto. After completion of all troubleshooting or testing proce-
dures all relays should be changed back to this setting. The 1=ON set-
ting will force the relay to the ON (energized) position. The 2=OFF
selection will force the relay to the OFF (de-energized) position.
The next screen displays the Relay Overrides for Relay 2. After press-
ing the "Enter" key the next relay will be displayed. All 20 Relay Over-
ride screens (including the AHU fan relay) are available by pressing the
"Enter" key after each setting is made.
Relay Overrides
Relay 2 Override: 0
[0=Auto 1=ON 2=OFF]
After the screen for relay 20 is displayed, the first Analog Output Over-
ride screen will be displayed.
Analog Output 1 Screen
Economizer Overrides
Analog Output #1
Override Volts: -1.0
[-1.0=Auto]
Press “Enter” and the next screen will appear for Analog Output #2.
Analog Output 2 Screen
Supply VFD Override
Analog Output #2
Override Volts: -1.0
[-1.0=Auto]
Press “Enter” and the next screen will appear for Analog Output #3.
Analog Output 3 Screen
Relief VFD Override
Analog Output #3
Override Volts: -1.0
[-1.0=Auto]
The default setting for normal operation is -1.0 volts. Voltages between
0 to 10.0 can be set for any of the Analog Output Overrides. Press “En-
ter” after making a setting change and the next Analog Output Override
screen will be displayed.