Technical Guide

Operator Interfaces

32

Setpoint Screen #14

HC Box Spts IDxxxx
Maximum EMS Setpoint
Offset...: xx

°

F

This screen is currently not used for this application.

Description

Minimum

Default

Maximum

EMS Setpoint

x

x

x

Setpoint Screen #15

Sensor Calibration
SPC: xxx.x

°

xxx.x

°

SAT: xxx.x

°

xxx.x

°

[SAT Only if Sensor]

The Thermistor Type III sensor readings can be calibrated. Enter a Posi-
tive value to increase a reading and a Negative value to decrease a read-
ing.

Note: The Supply Air Temperature calibration offset only op-

erates on the reading when the Box Controller has it’s’
own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from
a global broadcast, you will need to go to the air handler
to calibrate the temperature reading.

Description

Minimum

Default

Maximum

SPC [ Space Temp ]

-100.0

°

F

0.0

°

F

+100.0

°

F

SAT [ Supply Air ]

-100.0

°

F

0.0

°

F

+100.0

°

F

Status

Status Screen #1

HC Box v1.04 IDxxxx
Occupied Mode

Vent Mode

Belongs to Group # 1

Line 2

Unoccupied Mode

Occupied Mode

Override Mode

Override Pending

Damper Calibration

Remote Signal ON

Group Override

Line 3

OFF Mode

Vent Mode

Cooling Mode

Heating Mode

Warm-up Mode

Sensor Fail Mode

Line 4-

Belongs to Group # xx

No Group Affiliation

Status Screen #2

HC Box v1.04 IDxxxx
Zone Temp..: xx.x

°

F

Cooling Spt: xx.x

°

F

Heating Spt: xx.x

°

F

Line 2

Current Zone Temperature

Line 3

Currently active Cooling Setpoint based on the current
Occupied / Unoccupied mode of operation.

Line 4

Currently active Heating Setpoint based on the current
Occupied / Unoccupied mode of operation.

Status Screen #3

HC Box v1.04 IDxxxx
Slide Offset..: xx

°

F

H/C Demand.: xx.x

°

F

Line 2

If the optional Setpoint Slide Adjust is installed on the
Flush Mount Wall Sensor, this line will display the
current amount the Slide Offset is affecting the
Heating and Cooling Setpoints.

Line 3

Current Heating or Cooling Demand in the Zone
based on the current Heating and Cooling Setpoints
when compared to the current Zone Temperature.

Line 4

Current Supply Air Temperature received via
broadcast from the WMVAV controller or from the
VAVBox Controllers own installed Supply Air Sensor
on the AUX2 input.

Programming The VAVBOX Controller