INSTALLATION GUIDELINES SERIES HEATING CABLES

PAGE 7

THERMON...The Heat Tracing Specialists

®

TEP0118U-1111

Typical heat tracing system switching via interposing relay

or contactors

Power cable

1

Circuit switch with indicating lamp (padlockable)

2

Thermostat controller/limiter combination

3

Cold lead cables
In case heat dissipation of TES cable is lower than 16
W/m, the heating cable may be connected directly into
the junction box or thermostat without a cold lead. MI
cables always via cold lead cable.

5

4

Junction box

Cold lead junction
(see point 5)

6

Series heating cable

Star connection box

7

8

3a

3c

Thermostat controller

Thermostat limiter/limiter combination

3b

Thermostat limiter

to power

supply

panel

to power

supply

panel

or

single phase or

two phase

3-phase

Note:
For using thermostat limiters, see page 22-documentation