INSTALLATION GUIDELINES SERIES HEATING CABLES

PAGE 11

THERMON...The Heat Tracing Specialists

®

TEP0118U-1111

300 mm

For multiple parallel passes refer to illustration alongside.

heating cable

FT fixing tape / SS tie wire

Installation on pipe work

Temperature limiter sensor (if applicable)

In principle the heating cable is mounted parallel to
the pipe and fixed by means of FT fixing tape or SS tie
wire. Only if prescribed in the design, the cable must be
covered with aluminium tape.

Description:
FT-1L tape for max. 85 °C
FT-1H tape for max. 260 °C

Stainless steel tie wire to be supplied by electrical
contractor.

4 heating cables

3 heating cables

2 heating cables

1 heating cable

temperature

control

sensor

Note:
For using thermostat limiters, see page 22-documentation.