beautypg.com

Installation on safety valves – Thermon TESH User Manual

Page 18

background image

INSTALLATION GUIDELINES SERIES HEATING CABLES

PAGE 16

THERMON...The Heat Tracing Specialists

®

TEP0118U-1111

Installation on safety valves

For lines of 6" and larger
(for cable length see valve allowances on page 12)

pipe

exhaust

heating cable

A

A

Note:
- The heating cables should not touch or cross one

another.

- When prescribed in design apply aluminium tape over

the heating cable.

- Min. bending radius of the heating cable is 5-6 x cable

diameter.

- In each heating cable a loop must be made on the flange

if the pipe diameter allows for this. In case of process
heating, the valve and the piping up to section A - A to
be traced as an individual circuit.

FT fixing tape /
SS tie wire