Installation on valves – Thermon TESH User Manual
Page 14
INSTALLATION GUIDELINES SERIES HEATING CABLES
PAGE 12
THERMON...The Heat Tracing Specialists
®
TEP0118U-1111
Installation on valves
FT fixing tape /
SS tie wire
heating cable
NPS
½"
12
150
300
--
¾"
20
220
450
--
1"
25
300
600
300
1½"
40
450
600
450
2"
50
600
750
600
2½"
65
900
750
3"
80
1050
750
4"
100
1500
900
6"
150
2400
1050
8"
200
3300
1200
10"
250
4200
1350
12"
300
5000
1500
14"
350
5900
1650
16"
400
6900
1800
18"
450
8100
1950
20"
500
9000
2100
TYPICAL CABLE ALLOWANCES
PER VALVE *
(single pass) in mm
B
U
T
T
E
R
F
L
Y
N
O
M
I
N
A
L
P
I
P
E
S
I
Z
E
S
C
R
E
W
E
D
F
L
A
N
G
E
D
DN
Note:
- The heating cables should not touch or cross one
another.
- When prescribed in design apply aluminium tape over
the heating cable.
- Min. bending radius of the heating cable is 5-6 x cable
diameter.
- Apply additional SS tie wire/fixing tape in such a way
that heating cable makes close contact with the valve.
* Allowances for valves up to
600 Lbs and a single pass of
heating cable