INSTALLATION GUIDELINES SERIES HEATING CABLES

PAGE 17

THERMON...The Heat Tracing Specialists

®

TEP0118U-1111

Note:
- The heating cables should not touch or cross one

another.

- When prescribed in design apply aluminium tape over

the heating cable.

- Min. bending radius of the heating cable is 5-6 x cable

diameter.

- First mount the loop in the heating cable by means of tie

wire/fixing tape as shown.

- No heating cable to be installed on the manhole cover.

Installation on manholes

heating cable

FT fixing tape /
SS tie wire

This manual is related to the following products: