INSTALLATION GUIDELINES SERIES HEATING CABLES
PAGE 20
THERMON...The Heat Tracing Specialists
®
TEP0118U-1111
SS tie wire
max.
1000 mm
see detail A
see detail B
SS banding
aluminium tape
heating cable
SS punch strip
Detail A
Detail B (without heating cable)
1. Mount banding (not too tight) at the upper side of the
vessel or tank.
2. Push the required number of punch strips of sufficient
length between the banding and the tank vessel
wall. Hang up the punch strips to the banding. The
open side of the lips in the punch strips must point
downwards (see detail A). Space the punch strips
equally over the cir cumference of the vessel/tank
(max. spacing 750 mm).
3. Tighten the upper banding.
4. Bend the punch strips to the middle of the vessel/
tank bottom. Put a tie wire through the last slot of the
punch strips. Twist the ends of the tie wire until the
punch strips are tight against the wall and bottom (see
detail B).
5. First mount a banding at the lower side of the vessel/
tank and the other banding at a dis tance from each
other of max. 1000 mm.
6. Bend the lips of the punch strips upwards where
heating cable will be installed.
7. Place the heating cable in the upwards bended lips
(the lips are a support only and should not be
tightened over the heating cable!).
8. Connect the heating/cold lead cables into the power
supply box.
9. With a single phase + neutral or a two phase system,
the heating cable must be laid out along the vessel/
tank wall as a loop (so two heating cables parallel to
each other).
10. With a three phase system, the end of the three
cables must be connected to the end box, where a
star connection can be made.
11. Cover the heating cable over the total length with
aluminium tape.
Description:
SS punch strip
AL-20H aluminium tape
AL-30H aluminium tape
SS banding
SS banding seal
Stainless steel tie wire to be supplied
by electrical contractor
Installation on vessels or tanks
max. 750 mm
TES(H)/MI
Installation Guidelines
SERIES
HEATING CABLES
Subject to change without prior notice
Thermon Europe B.V.
Boezemweg 25
2641 KG Pijnacker
The Netherlands
Phone: +31-(0)15-36 15 370
Facsimile: +31-(0)15-36 15 379
www.thermon.com
Verify for the latest revision: www.thermon.com and select Europe
Installation Guidelines Series heating cable
rev.200609