For The Plumber

Drain Configuration:

Water cooled models must use a separate drain
tube from the reservoir/bin drain.

The water cooled condenser drain should not be
vented.

Drain tube material must be rigid and meet local
code.

Traps in the bin drain line without vents ahead of
them will cause poor draining.

The bin drain must be vented if there is a long
horizontal run (5’ or more).

All drains are gravity, and must have a minimum
fall of ¼" per foot of horizontal run.

Maintain the air gap required by local code
between the end of the drain tubes and the
building drain
receptacle.

Note: Drain tubing
should be insulated
to prevent
condensation from
forming on the
tubing.