OPERATION: Refrigeration

Low Condensing Temperature

The refrigeration system under low condenser air

temperatures is much the same as it is under

higher temperatures, with the exception that the

resulting low head pressures cause the head

pressure control to close off the liquid line between

the condenser and the receiver.

This forces more refrigerant into the condenser

(with a small amount of discharge gas going into

the receiver to maintain pressure until the head

pressure is built back up to the rated gauge

pressure of 180 psig). At that pressure the valve

opens up the liquid line from the condenser to the

receiver.

NME1854R & FME2404R

January 2000

Page 20

There are two separate refrigeration systems in this machine.

PUMP DOWN

During the pump down cycle (usually initiated by

the circuit board de-energizing the liquid line valve)

the discharge gases flow through their normal path

to the remote condenser, through the head

pressure control, and into the receiver.

At this point the refrigerant flow is stopped by the

closed liquid line valve. This action forces the

refrigerant into the receiver and keeps it out of the

compressor. The pump down continues until the

low pressure control turns the compressor off.

Head Pressure Control Valve - Normal

Temperature

From

Compressor

Valve

Disk

To

Receiver

From Condenser

Head Pressure Control Valve - Low

Temperature

From

Compressor

Valve

Disk

To

Receiver

From Condenser