Operational characteristics: cme1656 – Scotsman CME1356 User Manual
Page 34
![background image](https://www.manualsdir.com/files/803969/content/doc034.png)
Operational Characteristics: CME1656
Cycle Times (minutes):
System Pressures (PSIG):
Refrigerant Charge, R-404A
•
Air cooled: 64 ounces
•
Water cooled: 62 ounces (A thru E series)
•
Water cooled: 58 ounces (F series)
Typical Air Cooled Machine Amps
Single Phase
•
5 minutes into freeze: 17
•
Harvest: 15.5
Three Phase
•
5 minutes into freeze: 11
•
Harvest: 9
Typical Harvest Ice Weight
•
19.2 lb
Superheat (near the end of freeze)
•
The TXV will control a nominal superheat
point that can vary unit to unit from 11
o
F. to
17
o
F. While controlling that point the
superheat can also range + or - 4
o
F. without
affecting performance.
Water Cooled:
•
Discharge Pressure: 245 PSIG
•
Hi Pressure Cuts Out at: 450 PSIG
Air Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Freeze
15 - 17
18 - 20
Harvest
3
2 ½
Water Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Freeze
14 - 16
16 - 17
Harvest
2 ½
2 ½
Air Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze
21 - 23
34 - 36
Suction: Peak in Harvest
88 - 92
101 - 105
Discharge: 5 minutes into Freeze
210 - 220
285 - 295
Discharge: Minimum in Harvest
115 - 125
165 - 175
Water Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze
31 - 34
31 - 34
Suction: Peak in Harvest
75 - 85
80 - 90
Discharge:
245
245
CME1356 and CME1656
June 2002
Page 34