Adjustments – Scotsman CME1356 User Manual
Page 17

Adjustments
If there was a problem during Initial Start Up:
If an error light came on, check the following.
1. Water error.
A water error could have been determined by the
AutoIQ Controller if the inlet water valve does not
fill the reservoir, or if the water pump does not start
and lower the water level.
2. Refrigeration error.
A refrigeration error could have been determined
by the AutoIQ Controller if the water temperature
did not drop during the freeze cycle. The controller
will next check the compressor discharge
temperature, If the discharge temperature is too
low, the refrigerant error light will be switched on,
and the machine will Shut Down.
Note: Reset and restart the machine by
pushing and releasing the Off push button
switch, and then pushing and releasing the
freeze push button switch.
Splash Panel Positioning: It is critical that the
lower splash panel be properly positioned. If
removed during installation or start up, check that
it has been properlyreturned to its original position.
Insert Bottom Tabs in 5th
Slot of Cube Deflectors
Insert Into Slot
Lower Inner
Splash Panel
Lower Splash Panel Positioning
CME1356 and CME1656
May 2000
Page 17