Operational characteristics: cme1356 – Scotsman CME1356 User Manual
Page 33

Operational Characteristics: CME1356
Cycle Times (minutes):
System Pressures (PSIG):
Refrigerant Charge, R-404A
•
Air cooled: 64 ounces
•
Water cooled: 62 ounces (A thru E series)
•
Water cooled: 58 ounces (F series)
Typical Air Cooled Machine Amps
Single Phase
•
5 minutes into Freeze: 17
•
Harvest: 13
Three phase
•
5 minutes into Freeze 9.5
•
Harvest 8.5
Typical Harvest Ice Weight
•
16 lb
Superheat (near the end of freeze)
•
The TXV will control a nominal superheat
point that can vary unit to unit from 11
o
F. to
17
o
F. While controlling that point the
superheat can also range + or - 4
o
F. without
affecting performance.
Water Cooled:
•
Discharge Pressure: 245 PSIG
•
Hi Pressure Cuts Out at: 450 PSIG
Air Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Freeze
12 - 13
17 - 19
Harvest
2 ½ - 3
2
Water Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Freeze
13 - 14
15 - 16
Harvest
2 ½ - 3
2 ½ - 3
Air Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze
27 - 29
31 - 33
Suction: Peak in Harvest
82 - 84
92 - 94
Discharge: 5 minutes into Freeze
215 - 225
285 - 295
Discharge: Minimum in Harvest
165 - 175
165 - 175
Water Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze
28 - 30
29 - 31
Suction: Peak in Harvest
81 - 83
93 - 95
Discharge:
245
245
CME1356 and CME1656
June 2002
Page 33