beautypg.com

Precharged line routing – Scotsman C0522R User Manual

Page 12

background image

January 2014

Page 11

C0522 through C1030

Remote Condenser Models - User Manual
Precharged Line Routing

Do not connect the precharged tubing until all routing

and forming of the tubing is complete. See the

Coupling Instructions for final connections.

1. Each set of pre-charged tubing lines contains a 3/8”

diameter liquid line, and a 1/2” diameter discharge

line. Both ends of each line have quick connect

couplings, the end without access valves goes to the

ice maker.

Note: The openings in the building ceiling or wall,

listed in the next step, are the minimum sizes

recommended for passing the refrigerant lines

through.

2. Have the roofing contractor cut a minimum hole for

the refrigerant lines of 1 3/4”. Check local codes, a

separate hole may be required for the electrical power

supply to the condenser.

Caution: Do NOT kink the refrigerant

tubing while routing it.

3. Route the refrigerant tubes thru the

roof opening. Follow straight line routing

whenever possible. Excess tubing

may EITHER be coiled up INSIDE the

building OR cut out prior to connection

to the ice maker and condenser.

If the excess tubing is cut out, after re-

brazing the tubing must be evacuated

prior to connection to the ice maker or

condenser.

If the excess tubing is to be coiled, spiral

it horizontally to avoid excess trapping in

the lines.

5. Have the roofing contractor seal the

holes in the roof per local codes

Minimize

Outdoor Tubing

Keep Excess

Tubing Within

Conditioned

Space

This manual is related to the following products: