CTS-M17 Installation, Operation and Maintenance Manual

B84450-001-000 RG

May 12, 2005

6

1.6 Signal Range

The default gas range for the 4-20 mA signal is:

0 – 100 %LEL

max = 500 %LEL

This range is adjustable. Both the 4 mA level and the 20 mA level can be

reassigned through the menu system. Note that this adjustment does not change

the measurement resolution.

IMPORTANT: The Signal Range is the applied range of the 4-20

mA signal. The Display Range is independent of

the signal range.

1.7 Optional Relay Package

Two relays can be supplied; single pole double throw (SPDT; Form C) 1 Amp. Dry

contacts only. Configuration allows set point adjustment for actuation point, dead-

band, and delays, increasing or decreasing concentrations. The relay settings have

the same range as the display, and are independent of Analog Signal Range.

1.8 Default Conditions

Default conditions are those conditions, which occur:

During the one minute wait state on Power On.

In Fault status.

In menu tree.

In these situations the following conditions hold:

Signal set at 4.0 mA (or 2 Volts on Voltage Output mode)

Relays set to non-energized.

Digital communication show 0 %LEL; no alarm status and 4 mA equivalent

signal.

1.9 Sensing and Calibration

Sensor type: Catalytic bead

1.9.1 Calibration
The sensor shows a linear response to gas and therefore the unit is straightforward

to calibrate. Two gases are needed for calibration: Zero gas (clean air) and an

appropriate span gas. Adjustment is by two potentiometers on the circuit board.