RLE GD100 User Manual
Page 11

CTS-M17 Installation, Operation and Maintenance Manual
B84450-001-000 RG
May 12, 2005
10
Press the Down button to continue through the Relay 1 Settings
branch. Press Up to return to the Main Menu (and Relay 1 Settings
sub-menu branch).
4.2
Actuation Set Point
A
A
C
C
T
T
U
U
A
A
T
T
E
E
0
0
2
2
0
0
%
%
L
L
E
E
L
L
Choose the concentration of Gas in %LEL at which the relay will
actuate (energize). Minimum = 5 %LEL. Maximum = 60 %LEL in 5
%LEL increments.
Default = 20 %LEL
Up/Down scrolls up/down in the Relay 1 Settings branch.
4.3
De-Actuation Set point
D
D
E
E
A
A
C
C
T
T
0
0
1
1
5
5
%
%
L
L
E
E
L
L
Choose the concentration of the gas in %LEL at which the relay will
de-actuate (de-energize). Minimum = 5 %LEL. Maximum = 60 %LEL
in 5 %LEL increments.
Default = 15 %LEL.
Note: If the De-actuation set point is set at a higher
concentration than the Actuation set point, then the set
point function reverses and actuates on decreasing
concentrations.
Note: The software will not allow the user to set Actuation =
De-actuation.
4.4
Actuation Delay
A
A
C
C
T
T
-
-
T
T
I
I
M
M
E
E
0
0
0
0
m
m
i
i
n
n
Adjust the amount of time delayed before the relay is actuated after
the Actuation set point is reached. A maximum of 60 minutes is
possible, adjustable in 5-minute increments.
Default is 0000.
4.5
De-Actuation Delay