CTS-M17 Installation, Operation and Maintenance Manual

B84450-001-000 RG

May 12, 2005

13

1

1

0

0

0

0

%

%

L

L

E

E

L

L

This feature allows adjustment of the 20 mA point to different gas

concentrations.

Note: This setting only affects the concentration corresponding to 20

mA and not the range displayed on the LCD.

Maximum: 500 %LEL (see note 3 below)

Minimum: 0 %LEL

Note 1: An inverted response at the signal output can be achieved by

setting CONC4MA higher than CONC20MA.

Note 2: Changing the range in this fashion does not enhance the gas

measurement accuracy (e.g.: If there is an error of 1 %LEL,

it will still be an error of 1 %LEL even if the range is

reduced).

Note 3: Even though the 20mA point can be adjusted beyond

100%LEL, the product can only measure accurately to just

over 100%LEL, due to the response of the sensor. The range

up to 500%LEL is only provided for flexibility in the

installation.

IMPORTANT: Do not set CONC4MA and CONC20MA points

closer than 10 %LEL. If the unit finds these

points closer than 10%LEL on menu system exit,

the higher point will be automatically adjusted

until a minimum difference of 10%LEL is present.

8.

Gas Type Selection

G

G

A

A

S

S

T

T

Y

Y

P

P

E

E

M

M

e

e

t

t

h

h

a

a

n

n

e

e

Choose GAS TYPE from:

Methane

Butane

Ethanol

Genl LEL (General %LEL)

Propane

Hydrogen

Factory default is Methane.