Remko, Earthing of the condensation catch tray – REMKO Condensate Catch Tray With Oil Separator User Manual
Page 18
![background image](https://www.manualsdir.com/files/802513/content/doc018.png)
18
REMKO
WITH INTEGRATED OIL SEPARATOR
CONDENSATE CATCH TRAY
!
CAUTION
Make sure when installing the
outdoor component to provide for
the minimum clearance specified in
the operating manual.
In this case, the air intake side of
the outdoor component (backside
of the unit) requires a clearance of
at least 200 mm.
NOTE
Also observe the dimension
drawings for the respective outdoor
component in the respective
installation manuals.
!
CAUTION
The condensate catch tray must be
grounded!
Earthing of the condensation catch tray
In order to earth the condensation catch pan, proceed as follows:
1. Take the earth cable with the earth clip and cable shoe (Figure1)
included in the scope of delivery and fasten the cable shoe to the M6 earthing
screw (Fig. 2) mounted on the pan.
2. Attach the earthing clip in a suitable place on the inside of the galvanised
base in the outdoor unit (see Figure 3).
1 Earthing cable
2 Fasten the earthing cable to the pan
3 Attach the earthing clip
3. Re-assemble all side plates and com-
mission the system.