13 troubleshooting and customer service, 1 troubleshooting and customer service, Troubleshooting and customer service – REMKO WKF 85 User Manual

Page 75

background image

13

Troubleshooting and customer service

13.1

Troubleshooting and customer service

The unit has been manufactured using state-of-the-art production methods and tested several times to

ensure its correct function. However, in the event that malfunctions should occur, the device should be

checked against the following list. Please inform your dealer if the unit is still not working correctly after all of

the functional checks have been performed.

Fault

Possible causes

Remedial measures

The heat pump does

not start or switches

itself off

Power outage, under-voltage

Check the voltage and, if necessary,

wait for it to come back on

Defective mains fuse Master switch off

Exchange mains fuse, master switch on

Damaged mains cable

Repair by specialist firm

Power company off-period

Wait until the power-company off-

period is over and the heat pump starts

up as required

Operational temperature limits too low

or too high

Observe temperature ranges

Set-point temperature exceeded Incor-

rect mode

The set-point temperature has to be

higher than the heat-source tempera-

ture, check mode

Disconnect the outdoor module, then

establish the correct clamp order using

the connection plan Re-establish

voltage to the outdoor module. Also

make sure that the protective earth is

connected correctly.

Heat circuit pump fails

to switch off

Incorrect pump switching

Arrange to have pump switching

checked in "heating circuit" expert level

Heat circuit pumps fail

to switch on

Incorrect mode set

Check mode

Control PCB fuse in indoor module

switching cabinet faulty

Exchange the fuse on the left side of

the control PCB

Incorrect heating program set

Check heating program We recom-

mend the operating mode "heat" in the

cold heating season

Temperature overlapping, e.g. external

temperature greater than room temper-

ature

Observe temperature ranges

Red indicator lamp

Failure outdoor module

Contact customer service

75