2 units data wkf/wkf-compact 180, Remko wkf / wkf-compact, Units data wkf/wkf-compact 180 – REMKO WKF 85 User Manual
Page 10
2.2
Units data WKF/WKF-compact 180
Series
WKF 180
WKF-compact
180
Function
Heating or Cooling
System
Split-Air/Water
Heat pump manager
Smart-Control
Domestic water storage tank, enamelled
Optional
Series 300 l
Electric booster heating / rated output
kW
Optional/9,0
Optional/9,0
Domestic hot-water heating (changeover valve)
Optional
Series
Connecting oil-/ gas boiler
Optional
Optional
Heating capacity min / max
kW
3,1 - 17,7
Heating capacity / compressor frequency / COP f. A12/W35
kW/Hz/COP
16,02 / 56 / 5,33
Heating capacity / compr. frequency / COP
1)
f. A7/W35
kW/Hz/COP
14,02 / 56 / 4,53
Heating capacity / compr. frequency / COP
1)
f. A2/W35
kW/Hz/COP
9,32 / 56 / 3,53
Heating capacity / compr. frequency / COP
1)
f. A-7/W35
kW/Hz/COP
8,20 / 56 / 2,87
Heating capacity / compr. frequency / COP
1)
f. A-15/W35
kW/ Hz/COP
6,36 / 56 / 2,40
Heating capacity / compr. frequency / COP
1)
f. A7/W45
kW/Hz/COP
12,27 / 58 / 3,46
Heating capacity / compr. frequency / COP
1)
f. A7/W55
kW/Hz/COP
12,85 / 56 / 2,92
Heating capacity / compr. frequency / COP
1)
f. A-7/W55
kW/Hz/COP
6,99 / 56 / 1,94
Cooling capacity min. / max.
kW
2,8 - 15,0
Cooling capacity / compr. frequency / EER
2)
f. A35/W7
kW/Hz/EER
12,2 / 72 / 2,60
Cooling capacity / compr. frequency / EER
2)
f. A35/W18
kW/Hz/EER
12,7 / 38 / 3,81
Cooling capacity / compr. frequency / EER
2)
f. A27/W18
kW/Hz/EER
18,20 / 66 / 4,08
Service limits, heating
°C
-20 - +45
Service limits, cooling
°C
+15 - +45
Supply-temperature, heating water
°C
55
Min. Supply-temperature, cooling
°C
7
Refrigerant / pre-charge quantity outdoor unit
-- / kg
R 410A
2)
/ 2,85
Refrigerant / pre-charge quantity
for up to 10 m length of ordinary pipe
g / m
50
Refrigerant connection
Inches (mm)
3/8" (9,52) / 5/8" (15,9)
Max. refrigerant pipe length
m
75
Max. refrigerant pipe height
m
30
Power supply
V / Hz
400 / 3~ / 50
Max. current consumption
A
7,2
Rated current consumption for A7/W35 (per phase)
A
5,02
Rated power consumption for A7/W35
kW
3,09
REMKO WKF / WKF-compact