beautypg.com

2 units data wkf/wkf-compact 180, Remko wkf / wkf-compact, Units data wkf/wkf-compact 180 – REMKO WKF 85 User Manual

Page 10

background image

2.2

Units data WKF/WKF-compact 180

Series

WKF 180

WKF-compact

180

Function

Heating or Cooling

System

Split-Air/Water

Heat pump manager

Smart-Control

Domestic water storage tank, enamelled

Optional

Series 300 l

Electric booster heating / rated output

kW

Optional/9,0

Optional/9,0

Domestic hot-water heating (changeover valve)

Optional

Series

Connecting oil-/ gas boiler

Optional

Optional

Heating capacity min / max

kW

3,1 - 17,7

Heating capacity / compressor frequency / COP f. A12/W35

kW/Hz/COP

16,02 / 56 / 5,33

Heating capacity / compr. frequency / COP

1)

f. A7/W35

kW/Hz/COP

14,02 / 56 / 4,53

Heating capacity / compr. frequency / COP

1)

f. A2/W35

kW/Hz/COP

9,32 / 56 / 3,53

Heating capacity / compr. frequency / COP

1)

f. A-7/W35

kW/Hz/COP

8,20 / 56 / 2,87

Heating capacity / compr. frequency / COP

1)

f. A-15/W35

kW/ Hz/COP

6,36 / 56 / 2,40

Heating capacity / compr. frequency / COP

1)

f. A7/W45

kW/Hz/COP

12,27 / 58 / 3,46

Heating capacity / compr. frequency / COP

1)

f. A7/W55

kW/Hz/COP

12,85 / 56 / 2,92

Heating capacity / compr. frequency / COP

1)

f. A-7/W55

kW/Hz/COP

6,99 / 56 / 1,94

Cooling capacity min. / max.

kW

2,8 - 15,0

Cooling capacity / compr. frequency / EER

2)

f. A35/W7

kW/Hz/EER

12,2 / 72 / 2,60

Cooling capacity / compr. frequency / EER

2)

f. A35/W18

kW/Hz/EER

12,7 / 38 / 3,81

Cooling capacity / compr. frequency / EER

2)

f. A27/W18

kW/Hz/EER

18,20 / 66 / 4,08

Service limits, heating

°C

-20 - +45

Service limits, cooling

°C

+15 - +45

Supply-temperature, heating water

°C

55

Min. Supply-temperature, cooling

°C

7

Refrigerant / pre-charge quantity outdoor unit

-- / kg

R 410A

2)

/ 2,85

Refrigerant / pre-charge quantity

for up to 10 m length of ordinary pipe

g / m

50

Refrigerant connection

Inches (mm)

3/8" (9,52) / 5/8" (15,9)

Max. refrigerant pipe length

m

75

Max. refrigerant pipe height

m

30

Power supply

V / Hz

400 / 3~ / 50

Max. current consumption

A

7,2

Rated current consumption for A7/W35 (per phase)

A

5,02

Rated power consumption for A7/W35

kW

3,09

REMKO WKF / WKF-compact

10

This manual is related to the following products: