8
Connection of refrig-
erant lines
8.1
Connection of refrigerant lines
n
The outdoor- and the indoor units are con-
nected with two copper pipes of refrigerator
quality having the dimensions 3/8" = 9,52 mm
and 5/8" = 15,88 mm (REMKO special acces-
sory).
n
Observe the permitted bending radius for the
refrigerant pipes during installation in order to
prevent kinks. Never bend a pipe twice in the
same place in order to prevent embrittlement
or crack formation.
n
Assure suitable fastening and insulation when
laying the refrigerant pipes.
n
The copper pipes are to be flared to make the
connections to the units. In doing so, check
that the flare has the correct shape and suit-
able union nuts. (Fig. 53 to Fig. 55).
2
1
Fig. 53: Deburring the refrigerant line
1: Refrigerant line
2: Deburrer
1
Fig. 54: Flanging the refrigerant line
1: Flanging tool
Fig. 55: Correct flange shape
Copper piping Out-
side diameterer
Flare dimensions ø A
3/8" = 9,52 mm
12,4 - 12,8 mm
5/8" = 15,88 mm
21,9 - 22,3 mm
51