Minimum distances in mm for the outdoor modules WKF/WKF-compact
1
2
3
4
5
6
>= 250
>= 1500
>= 1500
>= 250
>= 250
>= 300
>= 600
>= 600
>= 250
>= 1500
>= 2000
Fig. 45: Minimum distances for installation of an outdoor module in mm for WKF/WKF-compact
1:
Against a wall, free flow air forward, backward
flow restriction
2:
Against a wall, facing the wall air outlet, flow
front restriction
3:
Freely between two walls, facing the wall outlet,
Sides: flow restrictions in front and rear
4:
In a niche, free flow air to the front, rear and
flow restriction on both sides.
5:
Before a covered wall, free flow air to the front,
rear and top of flow restrictions
6:
Before a covered wall, air outlet towards wall,
flow restrictions behind and above
1
2
3
4
>= 1500
>= 300
>= 600
>= 600
>= 600
>= 250
>= 600
>= 600
>= 1500
>= 250
>= 1500
>= 3000
>= 600
>= 250
>= 3000
Fig. 46: Minimum distances for installation of several outdoor modules in mm for WKF/WKF-compact
1:
Against a wall, facing the wall air outlet, flow
front restriction
2:
In a niche, free flow air to the front, rear and
flow restriction on both sides.
3:
Between two walls, facing the wall outlet and
other modules, Sides: flow restrictions in front
and rear
4:
Between two walls, air outlet towards wall, or
the external modules-free: flow restriction in
front, rear and internal modules on the sides.
43