Condensate draining and ensured discharge

3

2

4

9

5

5

11

100

6

8

7

10

10

12

12

1

Fig. 47: Condensate-, melt-water drainage and

transversely reinforced strip footing (sectional

drawing)

1:

Outdoor module

2:

Leg

3:

Condensation catch pan

4:

Floor bracket

5:

Transversely reinforced strip footing

HxBxD = 300x200x800 mm

6:

Gravel layer for seepage

7:

Condensate drainage-heating

8:

Drainage canal

9:

Protection tube for refrigerant pipes and elec-

trical interconnection (temperature resistant up

to at least 80 °C)

10: Depth of frost penetration

11: Drainag pipe

12: Soll

NOTICE!

The refrigerant lines must enter the housing

from the rear, side or front with the use of the

REMKO OA2 oil separator.

WKF/WKF-compact 120/180

E

B

B

A D

C

10

1

5

5

7

1

8

3

F

Fig. 48: Dimensioning of the transversely rein-

forced strip footing (Plan view)

Please see the terms 1,3,5,7,8 and 10 the legend

on Fig. 47

Dimensioning of the strip footing

(all values in mm)

Dim.

WKF/WKF-

compact

85

WKF/WKF-

compact

120

WKF/WKF-

compact

180

A

800

800

800

B

200

200

200

C

660

620

620

D

314

370

350

E

460

400

420

F

100

100

100

Condensate connection

If the temperature falls below the dew point, con-

densation will form on the finned condenser during

heating operation.

A condensate drip pan should be installed on the

underside of the unit to drain any condensate.

n

The condensate drain pipe to be installed on-

site must be installed with a in cline of at least

2 % for good drainage. If necessary, fit vapour

density insulation.

n

When operating the system at outdoor temper-

atures below 4 °C, care must be taken that the

condensate line is frost protected. The lower

part of the housing and condensate pan are to

be kept frost free in order to ensure permanent

drainage of the condensate. If necessary, fit

supplementary pipe heating.

n

After completed installation, check that the

condensate drainage is unobstructed and

ensure that the line is leak tight.