beautypg.com

Remko wkf / wkf-compact – REMKO WKF 85 User Manual

Page 26

background image

Loss in heating and cooling output

Depending on the length of the refrigerant piping and the difference in elevation between the indoor and out-

door units, there may be a loss in heating or cooling output. These can be calculated using the following dia-

grams.

Loss in heating output WKF/WKF-compact 85

25

30

15

20

10

5
0

-5

-10
-15
-20
-25
-30

0

5

10

15

20

25

30

35

40

45

50

A

B

[m]

[m]

100%

99%

97%

95%

95%

95%

95%

92%

92%

92%

+30 m

0 m

-30 m

Fig. 25: Loss in heating output WKF/WKF-compact 85

A: Difference in elevation

B: Length of refrigerant piping

Loss in cooling output WKF/WKF-compact 85

25

30

15

20

10

5
0

-5

-10
-15
-20
-25
-30

0

5

10

15

20

25

30

35

40

45

50

A

B

[m]

[m]

100%

98%

95%

95%

90%

90%

90%

87%

87%

87%

+30 m

0 m

-30 m

Fig. 26: Loss in cooling output WKF/WKF-compact 85

A: Difference in elevation

B: Length of refrigerant piping

REMKO WKF / WKF-compact

26

This manual is related to the following products: