Electrical protection for the system is imple-
mented in accordance with the information in
the technical data. Observe the required con-
ductor cross-sections!
n
All cables must be connected with the correct
polarity and strain relief.
n
Follow the connection schematic and the circuit
diagram.
n
Connect the two-wire control cable to terminals
F1, F2 and the earth terminal.
n
When connecting the control cable, make sure
that polarity is correct.
n
If the outdoor module is installed on a roof, it
and the supporting structure must be earthed
separately. (Connection to a lightning rod or a
concrete-footing earth electrode)
n
In the seriesWKF/WKF-compact 180 it must be
ensured that only the terminals L1(R), L2(S),
L3(T) and N are connected. (see Fig. 61).
2
3
1
Fig. 59: Connection terminals - outdoor module
WKF/WKF-compact 85
1: Display
2: Power supply 230V/1~ /50Hz
3: Control cable F1/F2
1
Fig. 60: Connection terminals - outdoor module
WKF/WKF-compact 120
1: Power supply 230V/1~ /50Hz
Fig. 61: Connection terminals - outdoor module
WKF/WKF-compact 180
NOTICE!
Make sure to connect the outdoor unit neutral
connector properly, otherwise the varistors on
the line-filter circuit board will be destroyed.
Temperature sensors
n
The number of sensors required can vary with
the type of system.
n
Observe the pertinent notes for the sensor
position found in the hydraulic schematic.
n
The standard model includes an external
sensor (S10), a submersible sensor (intended
for use as a custom hot-water sensor (S08)
and a sensor for a total inlet at the indoor
module.