The stop cocks supplied are to be positioned
directly at the connections for the heat pump
for the heater circuit inlet and return lines. The
shut-off valves each contain a thermometer.
Fig. 50: Shut-off valves
Turning the thermometer heads serves to close
or open the stop valves! The dial be brought
into the desired position.
n
Install the dirt traps delivered with the unit out-
side the heat pump in the return line. Ensure
that the dirt trap remains accessible for inspec-
tion.
n
Be sure to position one gate valve upstream
and another downstream of the dirt traps. This
ensures that the dirt traps can be checked at
any time without loosing water.
n
The dirt traps must be checked during every
service of the system.
n
Additionally, a hand-operated bleeder is
installed on the heat pump for additional
bleeding.
n
All visible metallic surfaces must be addition-
ally insulated.
n
Cooling mode via the heating circuit requires a
completely vapour diffusion tight insulation
along the entire length of the pipework.
n
All outgoing heating circuits, including the con-
nections for water heating, are to be secured
against circulating water by means of check
valves.
n
Before being placed in service, the system
must be thoroughly flushed. Conduct a seal
test and perform a thorough bleeding of both
the indoor unit and the entire system - repeat-
edly, if necessary.
Actual schemas for hydraulic integration can
be found on the internet at www.remko.de