11. Fault code P6: IPM power board safety shutdown

Is the voltage range
between P and N of
the IPM module OK?

Ensure the correct
supply voltage

Yes

Is the input voltage
between P and N of
the IPM module 230V
/ the frequency 50 Hz?

4-way valve

Temperature

Resistance Measuring point

20 °C

1.5 kΩ

Blue - Blue

Heating mode 0V AC
Cooling mode 230V AC

Note:

No

No

Are all the electrical
cables properly
connected?

Is the single-phase
bridge OK?
Take a measurement
with a multimeter
between “+” and the
two AC contacts and
between “-” and the
two AC contacts. Is the
resistance for the two
measurements 0

Ω?

Are the connecting
cables to the chokes
OK? Is the resistance of
the connecting cables

∞?

Check the fuses on the
power board. Are they
working OK?

Replace the
power board

Yes

Is the connection
between the main board
and IPM module OK?

No

Is the connection to the
compressor OK?

Establish a proper
connection

Yes

No

Establish a proper
connection

Replace IPM module.
Is fault still present?

Replace single-phase
bridge circuit

Replace connecting
cables

Yes

Replace main board.
Is fault still present?

Replace compressor.
Is fault still present?

Yes

Yes

Yes

No

No

Connect cables
properly
Is fault still present?

Yes

Yes

Yes

No

Yes

Replace the defective
fuse

No

41