Oil return measures

If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually
an oil pump bend is installed for
every 2.5 metres of height differ-
ence.

Oil return measures

Exterior unit

Oil pump bend

in suction pipe to

outdoor unit

1 x every 5

metres of rising

pipe

Radius:

50 mm

max. 5/10 m

Interior unit

Installation

Unit installation

The indoor unit is mounted face

down on four threaded rods. Take

into account the ceiling grid and

any other installations.

1. Use the dimensions of the ceil-

ing cassette (Fig. 6) to mark the

fixing points for the threaded

rods on structural parts ap-

proved to support the static

load above the suspended ceil-

ing.

2. Fit the indoor unit onto the

threaded rods and use the

lower nuts to level the unit

(Fig. 7)

.This ensures that the

condensate drains into the col-

Installation should only be
performed by authorised spe-
cialists.

NOTE

lection tray.

3. Fit the ceiling cassette approx.

2 cm higher than the surface of

the ceiling. (see Figure 8)

4. Make sure that clearance A,

(Fig. 8)

as specified in the table

below, is provided between the

underside of the suspended

unit and the underside of the

fastening surface.

5. Connect the refrigerant pipes,

electrical cables and condensa-

tion line to the indoor unit as

described below.

6. Check that the unit is level.

7. The final task is to tighten the

counternuts and attach the

cover.

Dimensions in

mm

RVD 351-

521DC

Distance A

35 mm

Distance B

25 mm

Mounting

the unit

620 x 400 mm

7 Hooking in the unit

8 Fastening the unit

Structural component

Structural component

B

A

6 Mounting the unit

400

610

All dimensions in mm

abaut 2 cm

Structural component

Dimensions in

mm

RVD 681-

1051DC

Distance A

35 mm

Distance B

25 mm

Mounting

the unit

620 x 400 mm

REMKO RVD...DC

18