Functional test and test run

During operation of the plant

operating parameters can be called

up on the outdoor unit display.

(only RVD 521-1051DC)

The following parameters are dis-

played successively:

RVD 521-1051 DC

- Frequency of the compressor

- Operating mode

- Level fan

- Current cooling/heating perforance

- Temperature sensor liquefier

- Temperature sensor hot gas

- Temperature sensor air inlet

- Power consumption outdoor unit

- Degree of opening for electronic

Expansion valve only RVD 521 DC

- error code

Proceed as follows to call up the

operating parameters:

1. Remove the cover from the

outdoor unit.

2. Switch all indoor units on and

select cooling mode and the
highest fan speed.

Frequency gauge

Temperature sensor air inlet

Temperature sensor liquefier

Operating mode

Operating mode fan

Cooling output - heating output
Outdoor unit / Indoor unit

Display

Frequency (Hz)

30

30

--

Stand by

60

60

Display

Mode Outdoor unit

0

Off

2

Cooling mode

3

Heating mode

4

Forced cooling

Display

Mode fan

0

Off

1

Low rotational speed

2

High rotational speed

Display

Cooling output

1

2.0-2.5 kW

2

2.5-3.0 kW

3

3.0-3.8 kW

4

3.8-5.0 kW

5

5.0-5.5 kW

6

5.5-6.1 kW

Display

Temperature

10

35-40 °C

11

40-45 °C

12

45-50 °C

13

50-55 °C

14

55-60 °C

15

60-65 °C

16

65-70 °C

Display

Temperature

15

-7.5 °C

20

-5.0 °C

25

-2.5 °C

30

0° C

35

2.5 °C

40

5.0 °C

45

7.5 °C

50

10.0 °C

55

12.5 °C

60

15.0 °C

65

17.5 °C

70

20.0 °C

75

22.5 °C

80

25.0 °C

85

27.5 °C

90

30.0 °C

95

32.5 °C

99

34.5 °C

Power consumption outdoor unit

Display

Power consump-

tion

44

6.0 A

46

6.2 A

54

7.4 A

55

7.6 A

58

7.8 A

62

8.0 A

66

8.6 A

67

8.8 A

68

9.0 A

70

9.2 A

72

9.5 A

76

10.0 A

78

10.2 A

80

10.4 A

82

10.6 A

84

11.0 A

88

11.6 A

92

12.0 A

94

12.2 A

Check button

Display
The display on the outdoor unit
PCB can call up the operating pa-
rameters of the plant in the above
order. In order to do so, press the
check button located next to the
display on the outdoor unit board.

Temperature sensor hot gas

Display

Temperature

10

35-40 °C

11

40-45 °C

12

45-50 °C

13

50-55 °C

14

55-60 °C

15

60-65 °C

16

65-70 °C

12. Check all the previously

described safety devices and

functions during the test run.

13. Enter the measured data in

the commissioning report.

in the commissioning report

and familiarize the operator

with the system.

14. Remove the pressure gauge.

Check that seals have been

fitted in the sealing caps.

NOTE

Press the TEST knob on the
outdoor unit board. This
serves to set the inverter to
max. refrigerating capacity.

15. Reinstall all parts which were

removed.