REMKO RVD xxx DC User Manual

Page 35

background image

Fault code

DISPLAY

Fault description

Required action

E0

EEPROM error

see page 85 / point 1

E2

Communication error between indoor unit and outdoor component

see page 85 / point 2

E3

Communication error on outdoor component main board

see page 86 / point 3

E4

Fault on the outdoor temperature sensor

see page 86 / point 4

E5

Compressor overvoltage protection

see page 86 / point 5

P0

Compressor overload protection (Klixon) tripped

P1

High pressure fault (from RVD 521 and up)

see page 87 / point 6

P2

Low pressure fault (from RVD 521 and up)

see page 88 / point 7

P3

Compressor overcurrent protection tripped

see page 89 / point 8

P4

Compressor overload protection (Klixon)

see page 90 / point 9

P5

Condenser outlet sensor triggered

see page 90 / point 10

P6

IPM power board safety shutdown

see page 91 / point 11

Fault displays shown on the outdoor component

1. Fault code E0: EEPROM error

No

Fit EEPROM properly

Is the EEPROM
fitted properly?

Yes

Replace outdoor
component main board

2. Fault code E2: communication error between indoor

unit and outdoor component

No

Establish the power
supply.

Is there voltage in the
indoor unit?

Yes

Reset the DIP switch
and switch for 5 min
without current.

Are the DIP switches
on the main board set
correctly?. See cover.

Yes

Is the cable connecting
the indoor unit and
outdoor component
properly connected?

No

Connect the cable
properly.

Replace the main board
for the indoor unit or
outdoor component

Yes

Is the cable connecting
the indoor unit and
outdoor component
damaged?

No

Yes

Replace the cable.

No

RVD 521-1051DC outdoor unit fault analysis

35