5 Installation inside buildings

Installation inside buildings

Ensure there is adequate heat
dissipation when placing the
outdoor component in cellars,
attics, adjoining rooms or halls
(Fig 5)

.

Install an additional fan with a
rated flow comparative to that
of the outdoor unit being in-
stalled in the room. This is used
in conjunction with ventilation
ducts to compensate any pres-
sure losses
(Figure 5).

Minimum clearances

Observe the minimum clearances to allow access for maintenance and
repair work and facilitate optimum air distribution.

500

1000

1000

1000

1000

E

C

B

A

D

Air intake

Air outlet

All values in mm

Minimum clearances

Ensure a continuous and unob-
structed air flow from outside,
preferably using sufficiently
large air intakes placed opposite
each other
(Figure 5)

.

Comply with any regulations
and conditions affecting the
statics of the building. If neces-
sary, fit acoustic installation.

Minimum clearance to snow

20 cm

Snow

Snow

The unit should be wall-mounted
in areas of heavy snowfall.

Installation should be at least 20
cm above the expected level of
snow to prevent snow from enter-
ing the outdoor component. An
optional wall bracket is available as
an accessory.

RVD 351DC AT RVD 521DC AT RVD 681DC AT RVD 1051DC AT

A

150 mm

B

900 mm

C

500 mm

D

150 mm

E

500 mm

17