Fault analysis – REMKO RVD xxx DC User Manual

Page 31

background image

Fault analysis

No

No

Yes

Yes

No

Yes

No

Yes

Is the resistance of the
vaporise sensor OK?
(white cable)
(Table 1 P92-94)?

No

Replace temperature
sensor

Replace indoor unit
main board

Yes

Note:

The room temperature sensor and vaporiser sensor
are brought together in a single connector, CN9

1. Operation light flashes at 5 Hz: fault on the

room temperature sensor

3. Timer light flashes at 5 Hz: communication

error between indoor unit and outdoor component

Establish the power
supply.

Is there voltage in the
indoor unit?

Is the connecting cable
shielded, and is it
earthed?

Use a shielded,
earthed cable

Is the cable connecting
the indoor unit and
outdoor component
properly connected?

Connect the cable
properly.

Is the cable connecting
the indoor unit and
outdoor component
damaged?

Replace the cable.

Replace the main board
for the indoor unit or
outdoor component

Is the resistance of the
temperature sensor OK?
(black cable)
(Table 1 P92-94)?

No

Replace temperature
sensor

Replace indoor unit
main board

Yes

2. Defrost light flashes at 5 Hz: fault on the

vaporiser sensor

No

Yes

Yes

Yes

4. Alarm light flashes at 5 Hz: float switch /

condensation pump

Replace float switch.
Error still exists?

Set the cooling mode
on the indoor unit and
run the system so a
few minutes.
If the error still exist?

Is the float switch
working properly?

Check the condensate
drain, whether it is
bent if necessary.
If the condensate drain
okay?

Replace the main board
for the indoor unit

Is the resistance of the
room sensor OK?
(Table 1 P92-94)?

Yes

No

Replace temperature
sensor

No

Condensate pump
exchange. Error still
exists?

Does the condensate
pump properly
appropriate?

Yes

No

Condensate drain
renew or repair

31