Function test and test run

During operation of the plant
operating parameters can be called
up on the outdoor unit display.
The following parameters are
displayed successively:

MVT 600 / 900 DC

- Frequency of the compressor
- Operating mode
- Current cooling / heating

performance
- Number of indoor units
- Temperature sensor air inlet
Liquefier
- Temperature sensor hot gas
- Power consumption outdoor unit
- Degree of opening for electronic
expansion valve no. 1
- Degree of opening for electronic
expansion valve no. 2
- Degree of opening for electronic
expansion valve no. 3

MVT 950 / 1050 DC

- Frequency of the compressor
- Performance requirements IT
- Mode AT
- Current cooling / heating

performance AT
- Operating mode fan AT
- Temperature sensor evaporator 4
- Temperature sensor evaporator 3
- Temperature sensor evaporator 2
- Temperature sensor evaporator 1
- Temperature sensor liquefier
- Temperature sensor air inlet
Liquefier
- Temperature sensor hot gas
- Power consumption compressor
- Degree of opening for electronic
Expansion valve no. 4
- Degree of opening for electronic
expansion valve no. 3
- Degree of opening for electronic
expansion valve no. 2
- Degree of opening for electronic
expansion valve no. 1
- Current voltage
- Number of indoor units
- Previous error message

Proceed as follows to call up the
operating parameters:

1. Remove the cover from the

outdoor unit.

2. Switch all indoor units on and

select cooling mode and the
highest fan speed.

Frequency gauge

Temperature sensor air inlet

Temperature sensor hot gas

Operating mode

Cooling - heating output AT / IT

Number of indoor units

Display

Frequency (Hz)

30

30

--

Stand by

60

60

Display

Mode AT

Mode fan

0

Off

Off

1

Cooling mode Low rotational speed

2

Heating mode High rotational speed

Display

No. indoor unit

1

1

2

2

3

3

4

4

Display

Cooling output

1

2.0-2.5 kW

2

2.5-3.0 kW

3

3.0-3.8 kW

4

3.8-5.0 kW

5

5.0-5.5 kW

6

5.5-6.1 kW

7

6.1-7.0 kW

8

7.0-7.5 kW

9

7.5-8.0 kW

10

8.0 kW

11

8.0-8.9 kW

Display

Temperature

10

35-40 °C

11

40-45 °C

12

45-50 °C

13

50-55 °C

14

55-60 °C

15

60-65 °C

16

65-70 °C

Display

Temperature

15

-7.5 °C

20

-5.0°C

25

-2.5°C

30

0°C

35

2.5°C

40

5.0°C

45

7.5°C

50

10.0°C

55

12.5°C

60

15.0°C

65

17.5°C

70

20.0°C

75

22.5°C

80

25.0°C

85

27.5°C

90

30.0°C

95

32.5°C

99

34.5°C

Power consumption outdoor unit

Display

Power

consumption

44

6.0 A

46

6.2 A

54

7.4 A

55

7.6 A

58

7.8 A

62

8.0 A

66

8.6 A

67

8.8 A

68

9.0 A

70

9.2 A

72

9.5 A

76

10.0 A

78

10.2 A

80

10.4 A

82

10.6 A

84

11.0 A

88

11.6 A

92

12.0 A

94

12.2 A

Check button

Display
The display on the outdoor unit
PCB can call up the operating
parameters of the plant in the
above order. In order to do so,
press the check button located
next to the display on the AT
board.